Time Response Information

Measuring Junctions

Grounded Junctions The thermo-elements are welded into the end cap using the same weld rod as the sheath material. Fast time response. Recommended for high-pressure applications.

Ungrounded Junctions The thermo-elements are welded together and are electrically isolated from the sheath. Recommended for applications where stray EMF’s would affect the reading.

Exposed Junctions The thermo-elements are welded together outside of the sheath. This provides the fastest time response but exposes the elements to contamination. Electrically isolated from the sheath.

______________________________________________________________________________

Approximate response time in seconds.

Values are for 2/3 of total temperature change from 0 to 100% as measured in water.

20-awg bare wire junction measured in gas.

Outside        Approximate          Approximate              Grounded           Ungrounded Diameter       Wire Gauge         Wall thickness              Junction               Junction___

.020                    38                    .003                             .02                            .03

.040                    32                    .006                             .04                           .13

.062                    28                    .009                            .22                            .40

.090                    25                    .012                            .33                            .68

.125                    22                    .017                            .50                           1.10

.188                    19                    .025                           1.00                          2.30

.250                    16                    .033                            2.20                          4.10

20 awg bare wire junction                                                                            .45